QFA4160 Room sensor for humidity (DC 0..10V) and temperature (DC 0..10V) with calibration certificate
Operating voltage AC 24 V / DC 13.5…35 V
• Signal output DC 0…10 V / 4…20 mA for relative humidity and temperature
• Very high measuring accuracy across the entire measuring range
• Capacitive humidity measurement
• Recalibration service
• Test function for loop test
• Range of use −40…+70 °C / 0…100 % r. h. with LCD display −25…+70 °C / 0…100 % r. h.
QFA3171D Room sensor for humidity (4…20 mA) and temperature (4…20 mA) for demanding requirements, with display
• Operating voltage AC 24 V / DC 13.5…35 V
• Signal output DC 0…10 V / 4…20 mA for relative humidity and temperature
• Very high measuring accuracy across the entire measuring range
• Capacitive humidity measurement
• Function test
• Range of use −40…+70 °C / 0…100 % r. h. with LCD display −25…+70 °C / 0…100 % r. h.
Use
QFA3171 Room sensor for humidity (4…20 mA) and temperature (4…20 mA) for demanding requirements
• Operating voltage AC 24 V / DC 13.5…35 V
• Signal output DC 0…10 V / 4…20 mA for relative humidity and temperature
• Very high measuring accuracy across the entire measuring range
• Capacitive humidity measurement
• Function test
• Range of use −40…+70 °C / 0…100 % r. h. with LCD display −25…+70 °C / 0…100 % r. h.
Use
QFA3160D Room sensor for humidity (DC 0…10 V) and temperature (DC 0…10 V) for demanding requirements, with displa
• Operating voltage AC 24 V / DC 13.5…35 V
• Signal output DC 0…10 V / 4…20 mA for relative humidity and temperature
• Very high measuring accuracy across the entire measuring range
• Capacitive humidity measurement
• Function test
• Range of use −40…+70 °C / 0…100 % r. h. with LCD display −25…+70 °C / 0…100 % r. h.
Use
QFA3160 Room sensor for humidity (DC 0…10 V) and temperature (DC 0…10 V) for demanding requirements
• Operating voltage AC 24 V / DC 13.5…35 V
• Signal output DC 0…10 V / 4…20 mA for relative humidity and temperature
• Very high measuring accuracy across the entire measuring range
• Capacitive humidity measurement
• Function test
• Range of use −40…+70 °C / 0…100 % r. h. with LCD display −25…+70 °C / 0…100 % r. h.
Use
QFA3101 Room sensor for humidity (4…20 mA) for demanding requirements
• Operating voltage AC 24 V / DC 13.5…35 V
• Signal output DC 0…10 V / 4…20 mA for relative humidity and temperature
• Very high measuring accuracy across the entire measuring range
• Capacitive humidity measurement
• Function test
• Range of use −40…+70 °C / 0…100 % r. h. with LCD display −25…+70 °C / 0…100 % r. h.
Use
QFA3100 Room sensor for humidity (DC 0…10 V) for demanding requirements
• Operating voltage AC 24 V / DC 13.5…35 V
• Signal output DC 0…10 V / 4…20 mA for relative humidity and temperature
• Very high measuring accuracy across the entire measuring range
• Capacitive humidity measurement
• Function test
• Range of use −40…+70 °C / 0…100 % r. h. with LCD display −25…+70 °C / 0…100 % r. h.
Use
? Operating voltage AC 24 V or DC 13.5…35 V
? Signal output DC 0…10 V / 4…20 mA for relative humidity
? Signal output DC 0…10 V / 4…20 mA / LG-Ni 1000 or T1 for temperature
? Accuracy of ? 3 % r.h. within comfort range
? Range of use ?15…?50 °C / 0…95 % r.h. (non-condensing)
RDF800KN/NF Touch Screen Flush-mount Room Thermostats with KNX Communications
For 2-pipe, 2-pipe with electrical heater, and 4-pipe fan coil units
For universal applications
For use with compressors in DX type equipment
• KNX bus communications (S-mode and LTE mode)
• Large display with backlight
• 2P / PI / P control
• Outputs for ON/OFF or 3-position control
• Outputs for 3-speed or 1-speed fan
• 2 multifunctional inputs for keycard contact, external sensor, etc.
• Independent function for window contact and presence detector
• Operating modes: Comfort, Economy and Protection
• Automatic or manual fan speed control
• Automatic or manual heating / cooling changeover
• Minimum and maximum limitation of room temperature setpoint
• Control depending on the room or the return air temperature
• Adjustable commissioning and control parameters
• Commissioning with Synco ACS, ETS4 or via local HMI
• Interoperation into Synco 700
• Integration into Desigo via group (ETS4) or via individual addressing
• Integration into third-party system via group addressing (ETS4)
• AC 230 V operating voltage
• RDF800KN: Mounting on round box, with min 60 mm diameter or recessed square 86 mm box with 60.3 mm fixing centers and min 40 mm depth
• RDF800KN/NF: Mounting on recessed square 86 mm box with 60.3 mm fixing centers and min 40 mm depth, requires additional mounting frame
RDF800KN Touch Screen Flush-mount Room Thermostats with KNX Communications
For 2-pipe, 2-pipe with electrical heater, and 4-pipe fan coil units
For universal applications
For use with compressors in DX type equipment
• KNX bus communications (S-mode and LTE mode)
• Large display with backlight
• 2P / PI / P control
• Outputs for ON/OFF or 3-position control
• Outputs for 3-speed or 1-speed fan
• 2 multifunctional inputs for keycard contact, external sensor, etc.
• Independent function for window contact and presence detector
• Operating modes: Comfort, Economy and Protection
• Automatic or manual fan speed control
• Automatic or manual heating / cooling changeover
• Minimum and maximum limitation of room temperature setpoint
• Control depending on the room or the return air temperature
• Adjustable commissioning and control parameters
• Commissioning with Synco ACS, ETS4 or via local HMI
• Interoperation into Synco 700
• Integration into Desigo via group (ETS4) or via individual addressing
• Integration into third-party system via group addressing (ETS4)
• AC 230 V operating voltage
• RDF800KN: Mounting on round box, with min 60 mm diameter or recessed square 86 mm box with 60.3 mm fixing centers and min 40 mm depth
• RDF800KN/NF: Mounting on recessed square 86 mm box with 60.3 mm fixing centers and min 40 mm depth, requires additional mounting frame
· KNX bus communications (S-mode and LTE mode)
• Backlit display
• 2P / PI / P control
• Outputs for on/off or 3-position control
• Outputs for 3-speed or 1-speed fan
• 2 multifunctional inputs for keycard contact, external sensor, etc.
• Operating modes: Comfort, Economy and Protection
• Automatic or manual fan speed control
• Automatic or manual heating/cooling changeover
• Minimum and maximum limitation of room temperature setpoint
• Control depending on the room or the return air temperature
• Adjustable commissioning and control parameters
• Commissioning with Synco ACS, ETS or via local HMI
• Integration into Synco
• Integration into Desigo and Apogee via group addressing (ETS) or via individual addressing
• Integration into third-party system via group addressing (ETS)
• AC 230 V operating voltage
• User and parameter settings can be retained or restored with power loss
· KNX bus communications (S-mode and LTE mode)
• Backlit display
• 2P / PI / P control
• Outputs for on/off or 3-position control
• Outputs for 3-speed or 1-speed fan
• 2 multifunctional inputs for keycard contact, external sensor, etc.
• Operating modes: Comfort, Economy and Protection
• Automatic or manual fan speed control
• Automatic or manual heating/cooling changeover
• Minimum and maximum limitation of room temperature setpoint
• Control depending on the room or the return air temperature
• Adjustable commissioning and control parameters
• Commissioning with Synco ACS, ETS or via local HMI
• Integration into Synco
• Integration into Desigo and Apogee via group addressing (ETS) or via individual addressing
• Integration into third-party system via group addressing (ETS)
• AC 230 V operating voltage
• User and parameter settings can be retained or restored with power loss
· KNX bus communications (S-mode and LTE mode)
• Backlit display
• 2P / PI / P control
• Outputs for on/off or 3-position control
• Outputs for 3-speed or 1-speed fan
• 2 multifunctional inputs for keycard contact, external sensor, etc.
• Operating modes: Comfort, Economy and Protection
• Automatic or manual fan speed control
• Automatic or manual heating/cooling changeover
• Minimum and maximum limitation of room temperature setpoint
• Control depending on the room or the return air temperature
• Adjustable commissioning and control parameters
• Commissioning with Synco ACS, ETS or via local HMI
• Integration into Synco
• Integration into Desigo and Apogee via group addressing (ETS) or via individual addressing
• Integration into third-party system via group addressing (ETS)
• AC 230 V operating voltage
• User and parameter settings can be retained or restored with power loss
·KNX bus communications (S-mode and LTE mode)
• Backlit display
• 2P / PI / P control
• Outputs for on/off or 3-position control
• Outputs for 3-speed or 1-speed fan
• 2 multifunctional inputs for keycard contact, external sensor, etc.
• Operating modes: Comfort, Economy and Protection
• Automatic or manual fan speed control
• Automatic or manual heating/cooling changeover
• Minimum and maximum limitation of room temperature setpoint
• Control depending on the room or the return air temperature
• Adjustable commissioning and control parameters
• Commissioning with Synco ACS, ETS or via local HMI
• Integration into Synco
• Integration into Desigo and Apogee via group addressing (ETS) or via individual addressing
• Integration into third-party system via group addressing (ETS)
• AC 230 V operating voltage
• User and parameter settings can be retained or restored with power loss
· KNX bus communication (S-mode and LTE mode)
· Backlit display
· 2P/PI/P control
· Outputs for On/Off, PWM, 3-position or DC 0…10 V control
· Outputs for 3-speed, 1-speed, or DC (DC 0…10 V) fan
· 3 multifunctional inputs for keycard contact, external sensor, etc.
· Operating modes: Comfort, Economy and Protection
· Automatic or manual fan speed control
· Automatic or manual heating/cooling changeover
· Minimum and maximum limitation of room temperature setpoint
· Control depending on the room or the return air temperature
· Selectable relay output functions (RDG16..KN)
· Built-in humidity sensor and humidity control (RDG165KN)
· Adjustable commissioning and control parameters
· Commissioning with Synco ACS, ETS or via local HMI
· Integration into Synco
· Integration into Desigo via group addressing (ETS) or via individual addressing
· Integration into third-party system via group addressing (ETS)
· Operating voltage:
RDG100KN: AC 230 V
RDG16..KN: AC 24 V
· KNX bus communication (S-mode and LTE mode)
· Backlit display
· 2P/PI/P control
· Outputs for On/Off, PWM, 3-position or DC 0…10 V control
· Outputs for 3-speed, 1-speed, or DC (DC 0…10 V) fan
· 3 multifunctional inputs for keycard contact, external sensor, etc.
· Operating modes: Comfort, Economy and Protection
· Automatic or manual fan speed control
· Automatic or manual heating/cooling changeover
· Minimum and maximum limitation of room temperature setpoint
· Control depending on the room or the return air temperature
· Selectable relay output functions (RDG16..KN)
· Built-in humidity sensor and humidity control (RDG165KN)
· Adjustable commissioning and control parameters
· Commissioning with Synco ACS, ETS or via local HMI
· Integration into Synco
· Integration into Desigo via group addressing (ETS) or via individual addressing
· Integration into third-party system via group addressing (ETS)
· Operating voltage:
RDG100KN: AC 230 V
RDG16..KN: AC 24 V