You are here:

SIEMENS,Room sensors, QFA41… ,for relative humidity and temperature with calibration certificates

Room sensors
QFA41…
for relative humidity and temperature with calibration certificates
• Operating voltage AC 24 V / DC 13.5…35 V
• Signal output DC 0…10 V / 4…20 mA for relative humidity and temperature
• Very high measuring accuracy across the entire measuring range
• Capacitive humidity measurement
• Recalibration service
• Test function for loop test
• Range of use −40…+70 °C / 0…100 % r. h. with LCD display −25…+70 °C / 0…100 % r. h.
Use
The QFA41… sensor is used in ventilation and air conditioning plants requiring:
• Very high accuracy and reliability for measuring relative humidity and temperature
• Regular recalibration and readjustment of the sensors
Examples:
• Storage and production facilities in the paper, textiles, pharmaceutical, chemical, electronics industries, etc.
• Laboratories
• Hospitals
• Computer centers
• Greenhouses

สินค้าที่เกี่ยวข้อง

Siemens VPP46..Q,Combi valves (PICV) PN25, externally threaded

systems
 With integrated differential pressure controller
 DN 10…DN32: Valve body made of dezincification resistant hot-pressed
brass (DZR)
 DN 40…DN 50: Housing made of spheroidal graphite iron
 Volumetric flow 30… 11500 l/h,
 Differential pressure range 15…600 kPa
 Internally threaded Rp conforming to ISO 7-1
 Externally threaded G conforming to ISO 228-1
 Version with pressure test points for Δp measurement (optional)
 Can be equipped with electro thermal or electromotive actuators
 SSA.. (3-position or DC 0…10 V)
 STA..3../STP..3.. (2-position or PDM)
 STA63../STP63.. (DC 0…10 V)
 SAY..1P03 (3-position or DC 0…10 V)

Siemens MXG462S..Modulating control valve with magnetic actuator‚ PN16

 

Short positioning time (< 2 s), high-resolution stroke (1 : 1000)
∂ Selectable valve characteristic: equal-percentage or linear
∂ High rangeability
∂ Operating voltage AC / DC 24 V
∂ Selectable standard signal inputs DC 0/2…10 V or DC 0/4…20 mA
∂ DC 0…20 V Phs phase-cut signal input for Staefa controllers
∂ Indication of operating state, visible from the outside
∂ Wear-free inductive stroke measurement
∂ Low friction, robust and maintenance-free
∂ Spring return facility: A↑ AB closed when de-energized
∂ Positioning control, position feedback and manual control
∂ Parts in contact with medium in CrNi steel
∂ MXG462S50-30 applications with demineralized water upon request

Siemens MXG461..P Modulating control valves with magnetic actuators, PN 16

Fast positioning time (<2 s), high-resolution stroke (1 : 1000), high rangeability
? Equal-percentage or linear valve characteristic (user-selected)
? Operating voltage AC / DC 24 V
? Switch-selected control signal DC 0/2…10 V or DC 4…20 mA
? DC 0…20 V phase cut control signal with SEZ91.6 external interface
? Indication of operating state, position feedback and manual control
? Wear-free inductive stroke measurement
? Fail-safe feature: A ? AB closed when de-energized
? Low friction, robust, no maintenance required

Modulating control valves with magnetic actuator,PN 16
MVF461H..
for hot water, high temperature hot water and steam
• Short positioning time (<2 s), high resolution (1 : 1000)
• Selectable valve characteristic: Equal-percentage or linear
• High rangeability
• Selectable standard interface DC 0/2…10 V or DC 0/4…20 mA
• Phase-cut signal input for Staefa controllers
• Position control and position feedback signal
• Wear-free inductive stroke measurement
• Spring return facility: A → AB closed when deenergized
• Low friction, robust and maintenance-free

Modulating refrigerant valves with magnetic actuator, PS45
MVL661..-..
Hermetically sealed, for safety refrigerants
· One valve type for expansion, hot-gas and suction throttle applications
· Hermetically sealed towards outside
· Selectable standard interface DC 0/2…10 V or DC 0/4…20 mA
· High resolution and control accuracy
· Precise positioning control and position feedback signal
· Short positioning time (< 1 s)
· Closed when deenergized
· Robust and maintenance-free
· Six valve sizes with kvs values from 0.25 to 12 m³/h
Use
The MVL661..-.. refrigerant valve is designed for modulating control of refrigerant
circuits including chillers and heat pumps. It can be used in expansion, hot-gas and
suction throttle applications as well as with all commonly used safety refrigerants (R22,
R134a, R227ea, R404A, R407C, R410A, etc.) and R744 (CO2).

 

Universal controller with P or PI action for heating, ventilation and air conditioning. 

Auxiliary functions

  • PI limiter function (absolute and relative limit)
  • Remote setpoint
  • Setpoint compensation
  • Winter/summer mode changeover (analogue or digital input)
  • Cascade control
  • Maximum priority for cooling / dehumidifying